Permit: T06CM05097

Parcel: 116154750


Addresses:

324 N HASMAN DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED PER DOUG
11/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MULTI-WIRE BRANCH CKT NOT TO TERMINATE ON SAME PHASE
2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED
3. NEED SEPARATE ARC FAULT BREAKER FOR BEDROOM CKT
11/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL CORRECT COVER @ CHIME TRANSFORMER
2. PROPERLY IDENTIFY PANEL DIRECTORY SO IT IS CLEAR & CORRECT (USE THE DIRECTORY ON COVER, ERASE OLD MARKINGS)
3. MULTI-WIRE BRANCH CKTS TO TERMINATE ON SEPARATE PHASES
4. DO NOT DOUBLE TAP ARC FAULT BREAKER, PROVIDE SEPARATE BREAKER FOR THIS CKT
5. ALL BEDROOM LIGHTS, SMOKE DETECTORS AND RECEPTACLES TO HAVE ARC FAULT PROTECTION
6. INSTALL MISSING PANEL COVER SCREWS
7. NEED PROPER CONNECTOR FOR HOOD CORD, CHECK DISHWASHER TOO.
8. IN BEDROOM, ONE RECEPTACLE MISSING MOUNTING SCREW, ONE RECEPTACLE HAS REVERSE POLARITY, SWITCHED RECEPTACLE MADE UP WRONG

ON ROOF
1. IDENTIFY DATA PLATES FOR ANY HEAT STRIPS
2. INSTALL CORRECT SIZE FUSES
3. STRAP FLEX WITHIN 12" OF TERMINATIONS
4. SEAL OPEN HOLE IN ROOF FOR STAT WIRE - ADD NEW ROOFTOP UNIT TO PERMIT