Permit: T06CM05078

Parcel: 13824078A


Addresses:

1471 W COMMERCE CT

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
03/24/2008 REINFORCED MASONRY PRE-GROUT Approved
02/25/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
OK TO GROUT DUMPSTER ENCLOSURE
09/27/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
ALL BUT DUMPSTER
09/26/2007 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LOADING DOCK NORTH & SOUTH WALL TO FULL HEIGHT
EAST SCREEN WALL TO 4'
06/26/2007 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE CONTINUOUSLY FROM SUPPORT AT ENDS OF WALLS AT LEAST ONE REBAR ON EACH SIDE OF CORNERS FROM FOUNDATION, IN ACCORDANCE WITH APPROVED PLANS VERTICAL REINFORCING ON TOP WALL ALL VERTICALS NEED TO COME FROM FOUNDATION AND NEED TO TRANSFER LOAD PATH TO FOUNDATION #4 @ 48" O.C OVERLAP WITH VERTICAL REINFORCING FROM FOUNDATION ON THESE MISSED REINFORCING PROVIDE EPOXY CONNECTIONS AND SPECIAL INSPECTION REPORT. VERIFY APPROPRIATE REINFORCING ON OPENINGS AND CONTROL JOINTS.

NOT APPROVED TO GROUT