Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT CORD AND PLUG CONNECT INSTANT HOT 2. CIRCUIT NOT SIZED PROPERLY FOR INSTANT HOT 3. PLAN SHOWS NO SIZE FOR INSTANT HOT 4. SEAL OPEN KNOCKOUT AIR HANDLER DISCONNECT 5. BOND AIR HANDLER DISCONNECT AND HEAT PUMP DISCONNECT 6. COMPLETE ALL ITEMS FROM INSPECTION ON 10/6/08 7. EXPLAIN EQUIPMENT GROUND ON LINE SIDE OF FUSE BONDING JUMPER ON LINE SIDE NOT SIZED PROPERLY. |