Permit: T06CM05057

Parcel: 11504568A


Addresses:

830 N 1ST AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM05057

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/24/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT CORD AND PLUG CONNECT INSTANT HOT
2. CIRCUIT NOT SIZED PROPERLY FOR INSTANT HOT
3. PLAN SHOWS NO SIZE FOR INSTANT HOT
4. SEAL OPEN KNOCKOUT AIR HANDLER DISCONNECT
5. BOND AIR HANDLER DISCONNECT AND HEAT PUMP DISCONNECT
6. COMPLETE ALL ITEMS FROM INSPECTION ON 10/6/08
7. EXPLAIN EQUIPMENT GROUND ON LINE SIDE OF FUSE
BONDING JUMPER ON LINE SIDE NOT SIZED PROPERLY.