Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM05057
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT CORD AND PLUG CONNECT INSTANT HOT 2. CIRCUIT NOT SIZED PROPERLY FOR INSTANT HOT 3. PLAN SHOWS NO SIZE FOR INSTANT HOT 4. SEAL OPEN KNOCKOUT AIR HANDLER DISCONNECT 5. BOND AIR HANDLER DISCONNECT AND HEAT PUMP DISCONNECT 6. COMPLETE ALL ITEMS FROM INSPECTION ON 10/6/08 7. EXPLAIN EQUIPMENT GROUND ON LINE SIDE OF FUSE BONDING JUMPER ON LINE SIDE NOT SIZED PROPERLY. |