Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 10/06/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) LABEL MAIN DISCONNECT 230.70 2) INSTALL MAIN BONDING SCREW 3) TERMINATE GROUNDING EQUIPMENT CONDUCTORS 4) PROTECT CONDUCTORS AT SUB PANEL 252.46 & 300.4 5) SECURE GROUNDING ELECTRODE CONDUCTOR TO SUB PANEL |