Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/20/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
10/19/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL SECURE UNISTRUT TO BLOCKING OF GAS PIPING & ROOF.
2. PROVIDE SEDIMENT TRAP AT ROOFTOP UNIT.
3. SHALL PROVIDE BLOCKING AND SUPPORT FOR CONDENSATE DRAIN AT 4' INTERVALS.
4. CONDENSATE SHALL TERMINATE 6" FROM AREA WHICH CAN ABSORB DRAINAGE.
5. SEAL OLD GAS PIPE PENETRATION THRU ROOF.
6. WATER HEATER REQUIRES MINIMUM 5' OF FLUE VENT PIPING, PENETRATION THRU ROOF TO BE DOUBLE WALL WITH FLASHING AND APPROVED DOUBLE WALL VENT CAP.
10/18/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
9:00 GATE LOCKED NO ACCESS