Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM05009
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/15/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SHALL SECURE WATER PIPING AT EXISTING WATER HEATER AND EXPANSION TANK. 2. PROVIDE MINIMUM 1" AIR GAP FOR WATER HEATER T&P DRAIN AT FLOOR SINK 3. SECURE DISHWASHER DRAIN HOSE 4. PROVIDE A MEANS TO CONTROL HOT WATER TEMPERATURE AT PUBLIC USE LAV BESIDES THE WATER HEATER MAX. TEMP 120 DEG. |