Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM05009
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO COVER ALL AREAS |
|
| 12/12/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RESTROOM 1/2 VENT TIE IN OK |
|
| 12/01/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IN RESTROOM #112 2" VENT STOPS ABOVE CEILING THIS VENT MUST CONNECT TO EXISTING VENT OR TERMINATE AT LEAST 6" ABOVE ROOF OK TO COVER WALLS. |
|
| 11/29/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED TO SEE TRAP ARM REVISED AT RESTROOM #120 OK TO COVER OTHER AREAS AFTER HOT INSULATION |
|
| 10/25/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/24/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TEST DOWN 2. EXPOSE ALL CONNECTIONS 3. TRAP ARM FOR LAV TO BE 1 1/2" 4. NOT INSTALLED PER PLAN -- NO REDLINES ON SITE. |