Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM05009

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/09/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/11/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER ONLY
11/30/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STILL HAVE BOXES WITH SCREWS NOT PER NEC 314.23
2. INSTALL ACCESS PANEL OR PROVIDE ACCESS BY OTHER MEANS TO EQUIPMENT REQUIRING ACCESS ABOVE CEILINGS.
3. FINISH ALL SOFFIT FRAMING AND COMPLETE RACEWAYS AS NEEDED.
4. REMOVE ALL ABANDONED WIRING -- INCLUDES LOW VOLTAGE - AS NEEDED L.W WIRING TO BE PROTECTED FROM STEEL STUDS - INSTALL NAIL PLATES FOR MC WHERE NEEDED NEC 300.5
11/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES TO BE MOUNTED PER NEC (2002) 314.23 A-1
2. BACK SUPPORT BOXES -- NEC 315.23A
3. REMOVE UNUSED WIRING IN WALLS.