Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM05009
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER ONLY |
|
| 11/30/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. STILL HAVE BOXES WITH SCREWS NOT PER NEC 314.23 2. INSTALL ACCESS PANEL OR PROVIDE ACCESS BY OTHER MEANS TO EQUIPMENT REQUIRING ACCESS ABOVE CEILINGS. 3. FINISH ALL SOFFIT FRAMING AND COMPLETE RACEWAYS AS NEEDED. 4. REMOVE ALL ABANDONED WIRING -- INCLUDES LOW VOLTAGE - AS NEEDED L.W WIRING TO BE PROTECTED FROM STEEL STUDS - INSTALL NAIL PLATES FOR MC WHERE NEEDED NEC 300.5 |
|
| 11/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES TO BE MOUNTED PER NEC (2002) 314.23 A-1 2. BACK SUPPORT BOXES -- NEC 315.23A 3. REMOVE UNUSED WIRING IN WALLS. |