Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04994
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/31/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE PREVIOUS INSPECTION ITEMS #2, 4 2. CABLES ENTERING CONTROL CABINET TO BE SECURED TO CABINET NEC 312.5 3. TYPE TC CABLE TO BE INSTALLED IN RACEWAY OR CABLE TRAY PER NEC 336.2 & 336.10 |
|
08/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PAINT BOOTH NOT TO BE USED BEFORE APPROVAL IN USE AT TIME OF INSPECTION 2. EQUIPMENT GROUND TO J-BOX UNDERSIZED - NEC 250.122 3. HOLE IN BACK OF J-BOX OVERSIZED, CONNECTOR/LOCKNUT DON'T FIT -- NEC 110.12 4. J-BOX UNDERSIZED - NEC 314.28 5. EQUIPMENT TO BE OPEN FOR INSPECTION 6. PROVIDE COMPLETED THIRD PARTY TEST REPORT INDICATING RESULTS |