Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04994
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CORRECTIONS 1, 2, 3 FROM PREVIOUS INSPECTION |
|
06/25/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. IDENTIFY PANEL DIRECTORY -- NEC 408.4 2. GROUND #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH - NEC 250.119 3. GROUND RODS TO BE EXPOSED FOR INSPECTION 4. FINISH PAINT BOOTH WIRING 5. PROVIDE PLAQUES COMPLYING WITH - NEC 230.2 E |
|
06/18/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* EMT (FEEDERS) TO ENTER INTO TOP OF GEAR/SAME VERTICAL SECTION JOHN 440-1597 BRIAN 349-4423 |