Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK FOR SHEETROCK |
|
| 02/05/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT 2) REMOVE SCREWS FROM DRYER VENT 3) SCREW EXHAUST DUCTS TO FANS |
|
| 01/16/2007 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE CONDENSATE DRAIN LINES PROVIDE WATER HEATER VENT DO NOT USE SCREWS IN DRYER VENT PROVIDE A SCREW IN EXHAUST FAN CONNECTIONS UNIT 2 DRYER VENT ELBOW UPSIDE DOWN. |