Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* PLUMBING FINAL OK OK FOR C OF O |
|
| 07/02/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS PIPING THRU ROOF REQUIRES ROOF JACK AND SHALL BE SUPPORTED CORRECTLY ON ROOF 2. GAS VALVE THEN FLEX AT UNIT ON ROOF 3. ALL PIPES THRU ROOF REQUIRE ROOF JACKS 4. PROVIDE AGA OR CSA APPROVED VALVE FOR DRYERS 5. CLEANOUTS REQUIRE FACTORY TAPPED PLUGS AND MACHINE SCREWS 6. PROVIDE COMBUSTION AIR FOR WATER HEATER NOT COMPLETE LIST |