Permit: T06CM04976

Parcel: 10714353B


Addresses:

451 E WILCOX LN #01

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/12/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1. OWNER IS AWARE OF REQUIREMENT FOR SEPARATE PERMIT ON SITE SEWER. OK TO COVER ABS SEWER TO PROPERTY LINE (WITH CLEAN FILL)
2. ABS DWV THRU ROOF OK
3. GAS PRESSURE TEST OK
TUBS OK
CLOSET FLANGES OK
4. MATERIAL SIZE AND TYPE REVISION
OK TO COVER ALL AREAS.
02/05/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PLAN CALLS FOR TYPE "M" COPPER
2) PLAN CALLS FOR 1 1/4" TO WATER HEATER
3) SECURE CLOSET FLANGES TO FLOOR
4) RED LINES FOR GAS INCOMPLETE
5) INSTALL PER PLAN OR REVISE PLAN-CON'T NOT READYS WILL RESULT IN REINSPECTION FEE
01/16/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. YOUR SITE PLAN IS INCOMPLETE. SEWER TERMINATES AT PROP. LINE
WHAT IS MAT'L TYPE, SIZE AND FINAL CONNECTION TO WHAT?
YARDWATER PIPING REQUIRES A SIZE AND MAT'L TYPE - SAME WITH GAS
2. SECURE TRAP ARMS AS CLOSE TO SWEEP AS POSSIBLE.
3. PLAN CALLS FOR 1/4" WATER SERVICE TO WH
PLAN CALLS FOR TYPE "M"
4. SECURE CLOSET FLANGES
STILL NO REDLINES ON GAS
01/11/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DWV NOT UNDER TEST, ALSO, TEST TUBS TO FLOOD LEVEL
2. SWEEPS REQUIRED ON TRAP ARMS AND ON TUB WASTE
3. PLAN CALLS FOR KIT TO VTR
4. CLOSET FLANGES NOT INSTALLED PER UPC IS #5
5. GAS PIPING NOT PER PLAN - REDLINE CHANGE OF METER LOCATION.
6. GAS TEST OK SUPPORT & SECURE GAS PIPING W/PIPE CLAMPS.
7. CORRECT SLOPE ON LAUNDRY DRAINAGE - SUPPORT HORIZONTAL PIPING.
8. CORRECT DAMAGED T&P DRAIN
9. SECURE WATER PIPING IN ALL AREAS INCLUDING LAUNDRY, ISOLATE FROM BRICK. SECURE SHOWER HEAD.
10. 60 PSI TEST ON WATER