Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BUBBLE COVERS ON OUTDOOR RECEPTACLES FRONT OF UNITS 2. NEED DETAILED PANEL SCHEDULES PER NEC 408.4 3. ALL BEDROOM OUTLETS TO BE ARC FAULT PROTECTED. THIS INCLUDES RECEPTACLES, LIGHTS, SMOKE DETECTORS, ETC. 4. INSTALL EXTENSION ON RECEPTACLE UNDER KITCHEN SINK 5. STRAP/SECURE ROMEX RUN THROUGH KITCHEN CABINETS 6. RE-IDENTIFY WHITE WIRE AT A/C DISCONNECTS USED AS PHASE CONDUCTOR 7. INSTALL BUBBLE COVERS ON ROOF TOP RECEPTACLES 8. SECURE/SUPPORT RECEPTACLE BOXES & EMT FOR ROOFTOP RECEPTACLES 9. SECURE/SUPPORT A/C DISCONNECTS & LIQUID TIGHT FLEX 10. SEAL ALL UNUSED OPENINGS IN BELL BOXES 11. INSTALL ROOF JACKS ON ALL PENETRATIONS |