Permit: T06CM04972

Parcel: 10713032A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04972

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
NEED TO PAY REINSPECTION FEE
1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN
2. AIM EMERGENCY LIGHTING
3. SUMP - IDENTIFY DISCONNECT, DON'T SWITCH NEUTRAL, GFI PROTECT RECEPTACLE, NOTCH COVER FOR CORDS

MAKE SURE ALL PREVIOUS CORRECTIONS COMPLETE
04/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AIM EMERGENCY LIGHTING SO IT IS EFFECTIVE
PATH OF EGRESS NOT UP IN AIR
2. WATER HEATER DISCONNECT TO HAVE PROPER FRONT WORKING CLEARANCE AND HAVE UNDERSIZED GROUND TO ENCLOSURE
3. EMERGENCY LIGHTING NOT WORKING IN SOME AREAS/NOT WIRED PER PLAN
4. SEAL UNUSED HOMERUN RACEWAY

PARTIAL INSPECTION ONLY -- ELECTRICIAN TO GO THROUGH AND MAKE SURE PER PLAN & CODE
03/31/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME
03/25/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME

GO THROUGH ALL WORK TO MAKE SURE PER CODE & PLAN
BEFORE CALLING IN. EQUIPMENT TO BE OPEN FOR INSPECTION
03/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
01/07/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*