Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM04972
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Not Applicable
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2008 | ELECTRIC - CABLE DROP | Not Applicable | IVRS - Inspection :* | |
| 02/27/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. SERVICE LATERAL CONDUCTORS TO BE SIZED FOR CALCULATED SERVICE LOAD - NEC 230.31(A) 2. BONDING CONDUCTOR FOR SERVICE SECONDARY RACEWAYS IS UNDER SIZED - NEC 250.102(C) 3. ALL CONNECTIONS ARE TO BE TORQUED PER MANUFACTURES LABEL - PROVIDE COMPANY LETTERHEAD AFTER YOU HAVE TORQUED THEM - NEC 110.3(B) 4. BONDING CONDUCTORS UNDER SIZED - NEC 250.102(C) 5. REMOVE ALL PAINT UNDER LUGS - NEC 250.8 6. INSTALL FUSES 7. GUTTER TO BE RAINTITE |
|
| 02/19/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
| 02/15/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
| 02/12/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* | |
| 01/14/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO CALL IN PROPER INSPECTION FOR SERVICE CABLE DROP 02050 2. INSTALL SERVICE SECONDARY CONDUCTORS FOR INSPECTION 3. BOND ALL SERVICE RACEWAYS AND ENCLOSURES - NEC 250.92 4. USE PROPER SIZE BONDING CONDUCTORS - NEC 250.102C 5. MYERS HUBS NOT LISTED FOR SERVICE SIZE BOND PATH - NEC 103 B, 250.92B 6. PROVIDE GROUNDING ELECTRODE SYSTEM FOR SERVICE (NEW) - NEC 250.50 7. BOND ALL METAL PIPING TO SERVICE - 250.104 8. INSTALL ADDRESS ON SERVICE 9. WORK NOT PER PLAN - PLAN DOES NOT SHOW 2ND CABINET DOES NOT SHOW CONDUCTOR FROM CABINET TO GUTTER, WIRING FROM GUTTER, ETC. WIRING TO BE PER PLAN OR REVISE PLAN AS NEEDED 10. INSTALL ALL FUSES 11. IDENTIFY "SERVICE DISCONNECTS" AS SUCH AND WHAT THEY DISCONNECT - NEC 230.72B 12. GROUNDED CONDUCTOR TO BE BONDED TO DISCONNECT ENCLOSURES - NEC 250.24C 13. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES - NEC 358.30 14. PROVIDE TORQUE LETTER FOR ALL CONNECTIONS 15. TIGHTEN ALL FITTINGS - NEC 358.42 16. INSTALL MAIN BONDING JUMPER FOR SERVICE - NEC 250.24 17. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6A PARTIAL INSPECTION ONLY WORK NOT COMPLETE AND NOT PER PLAN |