Permit: T06CM04972

Parcel: 10713032A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/17/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/04/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
12/03/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS -
NEC 330.30
OK CEILING TILES IN 3 OFFICES AFTER CORRECTION
DATA NOT IN
11/29/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. DEMO RECEPTACLE IN CEILING
2. HAVE TWO OVERFILLED J-BOXES
3. STRAP EMT WITHIN 36" OF BOXES

OK CEILING TILES RETAIL FLOOR AFTER CORRECTIONS
11/23/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/02/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK HARD LID COVER BATHROOMS
09/27/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
OK 8' PVC STUB AT S.E CORNER OF UTILITY ROOM