Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04972
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/04/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/03/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS - NEC 330.30 OK CEILING TILES IN 3 OFFICES AFTER CORRECTION DATA NOT IN |
|
| 11/29/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. DEMO RECEPTACLE IN CEILING 2. HAVE TWO OVERFILLED J-BOXES 3. STRAP EMT WITHIN 36" OF BOXES OK CEILING TILES RETAIL FLOOR AFTER CORRECTIONS |
|
| 11/23/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/02/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LID COVER BATHROOMS |
|
| 09/27/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK 8' PVC STUB AT S.E CORNER OF UTILITY ROOM |