Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM04970
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
01/31/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
01/29/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER SUPER |
|
01/25/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OUTSIDE LIGHTING DOES NOT COMPLY WITH OUTSIDE LIGHTING CODE .1087 ACRE LOT ALLOWED 5981 TOTAL LUMENS ? 1304 UNSHIELDED. YOU HAVE 4 EACH 100 IN UNSHIELDED FIXTURES FOR 6800 LUMENS. IF YOU FEEL YOUR FIXTURES ARE FULL CUT OFF FIXTURES THEN YOU MUST PROVIDE CERTIFICATION PER PARAGRAPH 4.7 OF THE OUTDOOR LIGHTING CODE 2) NEXT FAILURE MAY REQUIRE A REINSPECTION FEE |
|
01/24/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE OUTDOOR LIGHTING FIXTURE MANUFACTURE SPECIFIED SHEET |
|
01/22/2007 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE OUTDOOR LIGHT MANUFACTURE SPEC SHEET ON FIXTURES. IF FULL CUT OFF FIXTURES AT 100 ? YOU HAVE 6800 ? AND ARE ALLOWED ONLY 5995 TOO MANY FIXTURES. IF NOT FLO THOU YOU ARE ALLOWED 1308 ? AND 100 ? FIXTURE IS 1700 |
|
01/19/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE GRADING |