Permit: T06CM04969

Parcel: 10713032A

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM04969

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
11/19/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
11/15/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
2" PVC CW AND ABS SEWER PER REDLINES ON P-1
OK TO COVER
IRRIGATION ASSEMBLY MUST BE INSTALLED
11/14/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
SEWER AND YARD PIPING IS NOT ROUGH SOIL
08/14/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
OK FOR CONCRETE EXCEPT FOR WASHING MACHINE BRANCH
08/07/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. INSPECTOR NEEDS TO SEE ALL DEMO'D PIPE CAPPED OFF IN AN APPROVED MANNER.
2. WITH THREE PERMITS AT ONE ADDRESS IT IS IMPERATIVE TO CALL IN THE RIGHT INSPECTION CODE WITH THE CORRECT ACTIVITY NUMBER.
3. ABS DWV UNDER FLOOR, INSTALLED PER P-1 PLUMBING PAGE. WATER TEST ONE RISER TO TEN FEET.
4. P-1 SHOWS THREE RESIDENTIAL TYPE WASHING MACHINES FIXTURE UNIT CALCULATION SCHEDULE SHOWS EACH MACHINE AT 30FU'S -- PLEASE READ NOTE NUMBER FIVE ON TABLE 7-3 2003 UPC WHICH RATES EACH OF THE MACHINES AT 6 DFU'S - PLEASE REVISE PLAN AND MAKE NECESSARY FIELD CHANGES.
5. OK TO COVER THE REST