Permit: T06CM04969

Parcel: 10713032A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME
TOM 631-5574
03/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXTERIOR
1. SAFE OFF SIGN WIRING (W.P J.BOX)
2. NEED 2 BARREL LUGS FOR POLES & DO NOT OVERFILL WIRE NUTS (EQUIPMENT GROUND & GEC TO GO TO LUG & POLE)
3. AT SERVICE - MAKE UNUSED OPENINGS RAINTITE, NEED PARALLEL GROUNDS
03/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN SHOWS 2" RACEWAY TO PANEL WITH PULL STRING
2. CORRECTLY IDENTIFY EQUIPMENT AT PANEL & SERVICE
03/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*