Permit: T06CM04968

Parcel: 10713032A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04968

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/17/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
NEED TO PAY REINSPECTION FEE

1. MIN. SIZE GROUND 30 AMP. INSTA-HOT IS #10 CU
2. IDENTIFY WHITE USED AS HOT

MAKE SURE ALL PREVIOUS CORRECTIONS COMPLETE
04/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS NOT COMPLETE
03/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR INTERIOR

1. INSTA-HOT TO BE PROPERLY HARDWIRED ON MIN. 25 AMP
CKT AND PROVIDE DISCONNECTING MEANS
2. PANEL DIRECTORIES TO BE NEAT, LEGIBLE AND CORRECT
3. PANEL "B" DEAD FRONT COVER ALTERED
03/25/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN
2. PANEL DIRECTORIES NOT IN - TO BE NEAT, CORRECT, LEGIBLE
3. NEED PROPER DEAD FRONT COVER
4. IDENTIFY PANELS
5. FEEDER NEUTRAL PANEL "C" LUG NOT USED AS LISTED
6. PLANS SHOW #6 TO TTB
7. PLANS SHOW 112.5KW TRANSFORMER
03/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*