Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04968
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio NEED TO PAY REINSPECTION FEE 1. MIN. SIZE GROUND 30 AMP. INSTA-HOT IS #10 CU 2. IDENTIFY WHITE USED AS HOT MAKE SURE ALL PREVIOUS CORRECTIONS COMPLETE |
|
| 04/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETE |
|
| 03/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR INTERIOR 1. INSTA-HOT TO BE PROPERLY HARDWIRED ON MIN. 25 AMP CKT AND PROVIDE DISCONNECTING MEANS 2. PANEL DIRECTORIES TO BE NEAT, LEGIBLE AND CORRECT 3. PANEL "B" DEAD FRONT COVER ALTERED |
|
| 03/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. EMERGENCY LIGHTING NOT WORKING/NOT PER PLAN 2. PANEL DIRECTORIES NOT IN - TO BE NEAT, CORRECT, LEGIBLE 3. NEED PROPER DEAD FRONT COVER 4. IDENTIFY PANELS 5. FEEDER NEUTRAL PANEL "C" LUG NOT USED AS LISTED 6. PLANS SHOW #6 TO TTB 7. PLANS SHOW 112.5KW TRANSFORMER |
|
| 03/21/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/03/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |