Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2007 | MECHANICAL - INTERMEDIATE | Approved | ||
| 08/23/2007 | MECHANICAL - INTERMEDIATE | Denied | PRIOR TO FINAL INSPECTIONS: 1. INSTALL WATER HEATER 2. ADD SEDIMENT TRAPS TO FURNACES 3. PRIME PVC BEFORE GLUING 4. INCREASE DRAIN SIZE TO 1" WHEN COMBINING DRAINS 5. USE HARD PIPE FOR DRAIN 6. INSTALL SECONDARY DRAINS OR OVERFLOW SENSORS ON A/C COILS |
|
| 01/18/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | ||
| 01/17/2007 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/12/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |