Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM04964
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2007 | FRAMING | Approved | IVRS - Inspection :* | |
01/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADD SMOKIE IN MEDIA ROOM |
|
01/17/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) REMOVE INSULATION |
|
01/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BANG PLATES THROUGHOUT 2) BLOCK HVAC 3) SMOKIES MUST BE 6"-12" FROM CEILING 4) DUCT ABOVE CEILING LIGHT IN LIVING ROOM 5) FIRESTOP HOLES THROUGH TOP PLATES 6) FIRESTOP CEILING HEIGHT AT FAMILY ROOM/ENTRY, KITCHEN AND BREAKFAST ROOM 7) FIRESTOP KITCHEN FURR OUT 8) PROTECT GAS LINE IN KITCHEN 9) FLEX DUCT PROHIBITED 10) VACUUM BREAKERS ON HOSE BIBS 11) RUN CONDENSATE DRAINS 12) TPR LINE MUST EXIT BLDG 13) FLUE AT FURN/WATER HTR NOT CODE COMPIANT 14) DRYER DUCT EXCEEDS MAX. LENGTH 15) STOPPED INSPECTION |