Permit: T06CM04954

Parcel: 14101008C


Addresses:

10750 E BILBY RD 04


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM04954

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/13/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RESTROOM #122 CLOSET FLANGE OK
06/12/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
COMPLETE INSTALL OF CLOSET FLANGES
BEFORE CALLING FOR INSPECTION
04/04/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLOOR SINKS & TRAP PRIMERS IN KITCHEN OK
03/26/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SOUTH STAGE SINK OK IN WALL PIPING
2. NORTH & SOUTH STAGE GAS PSI TEST OK
03/14/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. ALL PUBLIC USE LAVS REQUIRE A FORM OF TEMPERING FOR HOT WATER WASTE & VENT THRU ROOF & WATER IN WALL AND OVERHEAD FOR ALL AREAS EXCEPT (2) STAGE AREAS OK

1. WILL NEED APPEAL FOR USE OF WATER LESS URINALS FROM BLD. OFFICIAL
03/12/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. TOO MUCH WATER ON FLOOR PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR DRAIN ARMS AT P-8
PROVIDE FLOOR MOUNTED CARRIER FOR URINALS.
TEST ALL PIPING THRU ROOF.
PROVIDE ACCESS TO APPROVED PLANS
LIST MAY NOT BE COMPLETE
3:30 NO PRESENCE ON SITE
03/07/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ADDITION OF 2" INDIRECT DRAIN FOR SANITIZE BOWL OF
3-COMP SINK IN WALL WITH VENT THRU ROOF WATER TEST OK
03/05/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER THRU GYM INTO WEST HALF & SOUTH
EXTERIOR OF GYM
03/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
KITCHEN AREA ADDITION OF DWV HANGERS OK
COMPLETE INSULATION IN WALL PRIOR TO COVERING
02/29/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV & WATER PIPING TEST THRU ROOF KITCHEN AREA AND WASHING MACHINE AREA
EAST BLOCK WALL OF GYM TO BLD EXTERIOR OK
EXCEPT 3-COMP SINKS TYPICALLY REQUIRE SANITIZE
BOWL TO BE INDIRECT DRAIN CONNECTION.