Permit: T06CM04954

Parcel: 14101008C


Addresses:

10750 E BILBY RD 04


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04954

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/26/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/02/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEED TO HAVE STEAM TABLES INSTALLED FOR FINAL
2. ALL OTHER INSPECTION ITEMS COMPLETED
3. CHECK WITH BUILDING INSPECTOR FOR TEMP C OF O
07/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
06/26/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
2. CHECK WITH BUILDING INSPECTOR FOR MOVING IN FURNITURE
06/25/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. UL LISTING NEEDED ON 4 STEAM TABLES
2. UL LISTING NEEDED ON ICE MAKERS
3. DISCONNECT MEANS FOR FAN COILS/OTHER EQUIPMENT
4. SEAL SEAL OFF'S FOR RACEWAY IN FREEZER
5. PANEL SCHEDULES W/ RM #
6. EM HEADS NOT WORKING
7. MOTOR SWITCHES FOR AIR CURTAIN
8. PROPER SIZE CONDUCTORS/DISC. FOR CONDENSING UNIT
9. MARK DISCONNECTS
06/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SEE WRITE UP FOR BUILDING #3
06/23/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SEE WRITE UP FROM T06CM04953 BLDG. #3
06/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ROOF INSPECTION
1. NEED PROTECTIVE BUSHING SEAL TIGHT
2. ADD ROOFTOP GFI
3. NEED DISCONNECTING MEANS MAKE UP AIR UNIT