Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* EF-28 NOT TO DESIGN CFM C-1 APPROVED |
|
| 06/23/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. AIR BALANCE REPORT, DUCT DETECTOR TEST REPORT 2. EXTERIOR COVERS ON DUCT SMOKE DETECTORS 3. FLUE PIPING TOO CLOSE TO COMBUSTIBLES 4. SEAL PENETRATIONS AT MINI SPLIT SYSTEM 5. PROVIDE HINGE KITS PER IMC 506.5.3 6. LABEL ALL RTU's |