Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04953
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* KITCHEN 1. DO NOT SEE LISTING MARK ON STEAM TABLES 2. DO NOT SEE LISTING MARK ON ICE MAKER 3. INSTALL DISCONNECTING MEANS FOR COIL UNITS WALK-IN/OTHER KITCHEN EQUIPMENT 4. SEAL RACEWAYS INTO WALK-INS 5. PANEL DIRECTORIES 6. EM LIGHTS WITH BUD LAMPS 7. NEED SWITCHES FOR AIR CURTAIN MOTORS 8. NEED PROPER SIZE CONDUCTORS FOR CONDENSING UNIT/INSTALL FUSES/MARK DISCONNECTS |
|
06/23/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MISSING EXITS 2. NEED BOX EXTENSIONS 3. RECEPT TO EXTEND PAST METAL PLATES 4. RECEPTS WITH NO POWER 5. FINISH EXTERIOR LIGHTS 6. NEED TO INSPECT LIFE SKILLS 7. PANEL SCHEDULES TO BE MORE DESCRIPTIVE |
|
06/20/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF INSPECTION 1. NEED PROTECTIVE BUSHING SEAL TIGHT 2. ADD ROOFTOP GFI 3. NEED DISCONNECTING MEANS MAKE UP AIR UNIT |