Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 01/04/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 3 - 4" PVC FROM TEP XFMR TO SES 2. SERVICE EQUIPMENT BEING INSTALLED DOES NOT MATCH APPROVED PLANS. WILL NEED REVISION FOR CHANGES PRIOR TO SERVICE BEING CLEARED 3. INSTALL WARNING RIBBON ABOVE SERVICE CONDUCTORS PER NEC 300.5 4. SCHEDULE 80 PVC IS REQUIRED ABOVE GRADE AND WHEN EXPOSED 5. PLAN CALLS FOR 600 MCM TEP WILL NOT CONNECT ANYTHING LARGER THAN 500 MCM I BELIEVE |
|
| 06/13/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUITS IN BLDG SLAB 2) UFER WAS CUT NEEDS TO BE REPAIRED |