Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM04950
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/04/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
01/04/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 3 - 4" PVC FROM TEP XFMR TO SES 2. SERVICE EQUIPMENT BEING INSTALLED DOES NOT MATCH APPROVED PLANS. WILL NEED REVISION FOR CHANGES PRIOR TO SERVICE BEING CLEARED 3. INSTALL WARNING RIBBON ABOVE SERVICE CONDUCTORS PER NEC 300.5 4. SCHEDULE 80 PVC IS REQUIRED ABOVE GRADE AND WHEN EXPOSED 5. PLAN CALLS FOR 600 MCM TEP WILL NOT CONNECT ANYTHING LARGER THAN 500 MCM I BELIEVE |
|
06/13/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUITS IN BLDG SLAB 2) UFER WAS CUT NEEDS TO BE REPAIRED |