Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM04950

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/04/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. OK 3 - 4" PVC FROM TEP XFMR TO SES
2. SERVICE EQUIPMENT BEING INSTALLED DOES NOT MATCH APPROVED PLANS. WILL NEED REVISION FOR CHANGES PRIOR TO SERVICE BEING CLEARED
3. INSTALL WARNING RIBBON ABOVE SERVICE CONDUCTORS PER NEC 300.5
4. SCHEDULE 80 PVC IS REQUIRED ABOVE GRADE AND WHEN EXPOSED
5. PLAN CALLS FOR 600 MCM TEP WILL NOT CONNECT ANYTHING LARGER THAN 500 MCM I BELIEVE
06/13/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK PVC CONDUITS IN BLDG SLAB
2) UFER WAS CUT NEEDS TO BE REPAIRED