Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM04934
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/29/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection : WATER TEST RETEST FOR ROOMS 118-119-109 THRU BUILDING OK WASTE & VENT |
|
01/24/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NO PIPING SHALL BE DIRECTLY EMBEDDED IN CONCRETE. 2. REMOVE CONCRETE FROM P-6 IN RMS 118-119 AND AT P-3 IN RM 109 3. PROVIDE FOAM WRAP PROTECTION 4. PIPING REPAIRS AND OFFSETS ARE TO BE TESTED. 5. YARD WATER PIPING NOT PER PLAN PROVIDE REDLINE ON PLANS AND PROVIDE A LETTER FROM ENGINEER ALLOWING THIS INSTALLATION AS WELL AS A DETAIL FOR CLEARANCES AROUND BACKFLOW DEVICE. 6. THERE SHOULD BE ROOM A HAND BETWEEN STUCCO AND RP SHUT OFF VALVES 7. PROTECT COPPER FROM STUCCO 8. ALL OTHER AREAS OK TO COVER 9. CLOSET FLANGES OK |
|
01/18/2007 | PLUMBING - INTERMEDIATE | Cancelled | CANCELLED BY ALEX |