Permit: T06CM04930

Parcel: 124050610

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/16/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/11/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
12/12/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/01/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING COVER FRONT AREA
10/18/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MC TO BE STRAPPED WITH MC STRAPS WITHIN 12" OF TERMINATIONS -- NEC 330.30 AND SUPPORTED AT MAXIMUM 6' INTERVALS NEC 330.30
2. FILL UNUSED OPENINGS IN BOXES -- NEC 110.12
ALSO, FINISH MAKE UP AND CLOSE ALL J-BOX COVERS ON FIXTURES.
3. ALL J-BOXES IN CEILING TO BE ACCESSIBLE -- NEC 110