Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04930
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
01/11/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
12/12/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/01/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING COVER FRONT AREA |
|
10/18/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MC TO BE STRAPPED WITH MC STRAPS WITHIN 12" OF TERMINATIONS -- NEC 330.30 AND SUPPORTED AT MAXIMUM 6' INTERVALS NEC 330.30 2. FILL UNUSED OPENINGS IN BOXES -- NEC 110.12 ALSO, FINISH MAKE UP AND CLOSE ALL J-BOX COVERS ON FIXTURES. 3. ALL J-BOXES IN CEILING TO BE ACCESSIBLE -- NEC 110 |