Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04926
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* OK TO TILE |
|
12/11/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. 2X4 & 2X2 FIXTURES TO BE ATTACHED TO GRID -- 410.16 2. SUPPORT VDV CABELING 725.6, 760.6, 800.6, 725.3, 760.3, 800.3 3. DO FIREWALL PENETRATIONS NEED TO BE SEALED |