Permit: T06CM04903

Parcel: 10511040D

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM04903

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
02/14/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
02/07/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR TO SERVICE IS MISSING
2) IN GUTTER-SERVICE CONDUCTORS TO PASS THROUGH SAME NIPPLE, NIPPLES APPEAR OVER FILLED-NEC 300.3 B, NEC TABLE 1 CHAPTER 9 NOTE 4
3) BOND CONDUCTORS FOR NIPPLES CT CAN TO DISCONNECTS ARE UNDERSIZED-NEC 250.102 C
4) DO NOT STACK BOND LUGS IN DISCONNECTS-NEC 110.3 B
5) BOND NEUTRAL TO DISCONNECT (BOND SCREW) NEC 250.24 B
6) INSTALL FUSES IN DISCONNECTS NEC 310
7) IDENTIFY DISONNECTS AS SERVICE DISCONNECTS-NEC 230.70 B
8) ARRANGE BONDING CONDUCTOR INTO CT CAN FROM GUTTER TO PREVENT OBJECTIONABLE CURRENT NEC 250.6