Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 02/07/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR TO SERVICE IS MISSING 2) IN GUTTER-SERVICE CONDUCTORS TO PASS THROUGH SAME NIPPLE, NIPPLES APPEAR OVER FILLED-NEC 300.3 B, NEC TABLE 1 CHAPTER 9 NOTE 4 3) BOND CONDUCTORS FOR NIPPLES CT CAN TO DISCONNECTS ARE UNDERSIZED-NEC 250.102 C 4) DO NOT STACK BOND LUGS IN DISCONNECTS-NEC 110.3 B 5) BOND NEUTRAL TO DISCONNECT (BOND SCREW) NEC 250.24 B 6) INSTALL FUSES IN DISCONNECTS NEC 310 7) IDENTIFY DISONNECTS AS SERVICE DISCONNECTS-NEC 230.70 B 8) ARRANGE BONDING CONDUCTOR INTO CT CAN FROM GUTTER TO PREVENT OBJECTIONABLE CURRENT NEC 250.6 |