Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/10/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) OK TO INSULATE 2) FIREPLACE NEEDS TO BE INSTALLED PRIOR TO FINAL FRAME APPROVAL 3) T/P LINE MUST RUN DOWN HILL AT ALL POINTS AND MUST BE HARD PIPED (NO FLEX LINE) 4) WATER HEATER B-VENT REQUIRES MINIMUM 1" CLEARANCE TO COMBUSTIBLES 5) DRIP LEG REQUIRED ON WATER HEATER GAS LINE |
|
| 04/27/2007 | FRAMING | Partial Approval | IVRS - Inspection :* |