Permit: T06CM04902

Parcel: 133071300

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/22/2007 FRAMING Approved IVRS - Inspection :*
05/10/2007 FRAMING Partial Approval IVRS - Inspection :*
1) OK TO INSULATE
2) FIREPLACE NEEDS TO BE INSTALLED PRIOR TO FINAL FRAME APPROVAL
3) T/P LINE MUST RUN DOWN HILL AT ALL POINTS AND MUST BE HARD PIPED (NO FLEX LINE)
4) WATER HEATER B-VENT REQUIRES MINIMUM 1" CLEARANCE TO COMBUSTIBLES
5) DRIP LEG REQUIRED ON WATER HEATER GAS LINE
04/27/2007 FRAMING Partial Approval IVRS - Inspection :*