Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 06/16/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DETAIL 207 NOT MET ON NEW STORAGE ROOM AND OFFICE GUEST ROOM 2) NEED DBL STUD AT BEAM BEARING AT GARGE TO PATIO N/W CORNER 3) NEED TO NAIL DBL STUDS AT ALL HOLDOWNS FOR SOLE PLATE TO PLATE 4) MISSING ANCHOR BOLTS IN DINING ROOM PER SHEARWALL PLAN 5) NEED HTT16 INSTALLED IN STORAGE ROOM 6) DINING ROOM H.D. WILL NEED A RETRO-CANNOT BE ON A WINDOW TRIMMER |
|
| 06/11/2008 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* INSPECTED A35 AT LEDGERS ON BEARING WALL AT STORAGE |