Permit: T06CM04901

Parcel: 117020590


Addresses:

1045 N 3RD AV


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM04901

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/14/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/16/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DETAIL 207 NOT MET ON NEW STORAGE ROOM AND OFFICE GUEST ROOM
2) NEED DBL STUD AT BEAM BEARING AT GARGE TO PATIO N/W CORNER
3) NEED TO NAIL DBL STUDS AT ALL HOLDOWNS FOR SOLE PLATE TO PLATE
4) MISSING ANCHOR BOLTS IN DINING ROOM PER SHEARWALL PLAN
5) NEED HTT16 INSTALLED IN STORAGE ROOM
6) DINING ROOM H.D. WILL NEED A RETRO-CANNOT BE ON A WINDOW TRIMMER
06/11/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
INSPECTED A35 AT LEDGERS ON BEARING WALL AT STORAGE