Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPLY STRAIN RELIEF FOR RECEPTACLE PENDANT. 2. STRAP MC WITHIN 12" OF TERMINATIONS & SUPPORT OFF GRID - PER NEC 330.30 3. MULTI-WIRE BRANCH CKT'S WITH COMMON NEUTRAL, HOTS NEED TO TERMINATE ON SEPARATE PHASES. 4. USE EQUIPMENT GROUND TO GROUND ALL EQUIPMENT/BOXES. 5. COMPLETE PREVIOUS CORRECTIONS. |
|
| 12/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUCTORS IN RACEWAYS NEED TO BE DERATED - NEC 310.15 B2 2. INSTALL LOCKNUT FOR RACEWAY AT PANEL (1" EMT) 3. PROPERLY GROUND METAL BOXES 4. PROVIDE LADDER FOR CEILING INSPECTION 5. WALLS COVERED WITHOUT INSPECTION 6. REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK |