| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* CORRECTIONS MADE OK OK FOR GAS UCC LEFT AT METER SW GAS 889-1888 |
|
| 11/13/2006 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 11/06/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. UNABLE TO LOCATE PLAN OR PERMIT. 2. PVC YARDWATER REQUIRES A MINIMUM OF 12" OF COVER. 3. REQUIRE AVB'S ON ALL HOSE BIBBS. 4. WRAP PIPE PENETRATION AND SEAL EXT. WALL 5. SUPPORT ALL UNDER FLOOR PIPING. 6. COMPLETE ALL PIPING TEST ALL PIPING 7. HAVE GAS 03050 ADDED TO YOUR PERMIT |