Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. USE CONNECTOR ON DISH & DISP CORDS - NEC 400.14 2. INSTALL RANGE ANTI-TIP DEVICE -- NEC 110.3B 3. MASTER BATH LIGHT MISSING/NOT PROPERLY INSTALLED 4. PROVIDE ARC FAULT PROTECTION FOR ALL BEDROOM WIRING - NEC 210.12 5. AC'S ON ROOF A. INSTALL CORRECT SIZE FUSES - NEC 110.3B, NEC 310 B. STRAP FLEX - NEC 356.30 C. PROVIDE SERVICE RECEPTACLE - NEC 210.63 6. SUB-PANEL A. PROVIDE APPROVED WIRING METHOD FOR FEEDERS NEC 300.3 B. NEUTRAL TO BE ISOLATED FROM GROUNDS - NEC 250.24 A 5 7. DISPOSAL CORD 36" MAX. LENGTH - NEC 400 HAVE LICENSED ELECTRICAL CONTRACTOR DO WORK. 8. KITCHEN ISLAND TO HAVE RECEPTACLES - NEC 210.52 C 2 9. CRIMP SLEEVES STILL DON'T HAVE PROPER CRIMP TOOL FOR EQUIPMENT GROUNDS - NEC 110.3B A REINSPECTION FEE MAY BE CHARGED IF NOT CORRECT NEXT INSPECTION. 10. ADD HARD WIRED, INTERCONNECTED SMOKE DETECTORS IN HALL, BEDROOMS (3) |