2808 E ADAMS ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. USE CONNECTOR ON DISH & DISP CORDS - NEC 400.14
2. INSTALL RANGE ANTI-TIP DEVICE -- NEC 110.3B
3. MASTER BATH LIGHT MISSING/NOT PROPERLY INSTALLED
4. PROVIDE ARC FAULT PROTECTION FOR ALL BEDROOM WIRING - NEC 210.12
5. AC'S ON ROOF
A. INSTALL CORRECT SIZE FUSES - NEC 110.3B, NEC 310
B. STRAP FLEX - NEC 356.30
C. PROVIDE SERVICE RECEPTACLE - NEC 210.63
6. SUB-PANEL
A. PROVIDE APPROVED WIRING METHOD FOR FEEDERS
NEC 300.3
B. NEUTRAL TO BE ISOLATED FROM GROUNDS -
NEC 250.24 A 5
7. DISPOSAL CORD 36" MAX. LENGTH - NEC 400
HAVE LICENSED ELECTRICAL CONTRACTOR DO WORK.
8. KITCHEN ISLAND TO HAVE RECEPTACLES - NEC 210.52 C 2
9. CRIMP SLEEVES STILL DON'T HAVE PROPER CRIMP TOOL FOR EQUIPMENT GROUNDS - NEC 110.3B

A REINSPECTION FEE MAY BE CHARGED IF NOT CORRECT NEXT INSPECTION.

10. ADD HARD WIRED, INTERCONNECTED SMOKE DETECTORS
IN HALL, BEDROOMS (3)