Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/20/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* DON'T CALL UNTIL FINAL |
|
| 11/16/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY TERMINATE ALL EQUIPMENT GROUNDS AND USE PROPBER CRIMP TOOL 2) USE PROPER CONNECTOR FOR CABLES ENTERING METAL BOXES 3) BATH GFI TO BE DEDICATED 4) FINISH KITCHEN SINK W. RING, KITCHEN LIGHTING |
|
| 11/13/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE PROPERLY SIZED STRAPS FOR BOND/G.E.C 2. BURY CONDUCTOR MINIMUM 12" OR SECURE TO STRUCTURE. 3. SERVICE CONDUCTORS TO HAVE MINIMUM 10' CLEARANCE TO GRADE AND 3' OVER ROOF, INSTALL LISTED GUY KIT FOR MAST. 4. ANCHOR SERVICE AND MAST TO STRUCTURE BETTER. 5. INFERIOR WIRING NOT APPROVED FOR COVER - UNCOVER AS NEEDED FOR INSPECTION. |
|
| 11/06/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE VERIFY PERMIT FOR NEW WIRING TO INTERIOR. 2. A PERMANENT METAL ADDRESS LABEL IS NEEDED. 3. STRAP GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE. 4. CONNECT GAS BOND AND VERIFY WATER BOND. 5. RISER HARDWARE TO BE 1/4" MINIMUM 6. TIGHTEN ACORN CLAMPS AND INSTALL AS PER MANUFACTURE 7. NO CIRCUITS IN THE PANEL AT THIS TIME. |