Permit: T06CM04858


Addresses:

8265 S HOUGHTON RD

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
03/26/2008 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
03/05/2008 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) PROVIDE LETTER OF TORQUE FOR SWITCH GEAR
2) RECEIVED LETTER FROM ENGINEER FOR SERVICE CONDUCTOR SIZE
02/21/2008 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
SERVICE CONDUCTOR SIZE NOT SHOWN ON PLANS
PLANS CALL FOR 1000 AMP SERVICE
HAVE 3 SETS OF 500 MCM AL INSTALLED ONLY GOOD FOR
930 AMPS. HAVE ENGINEER PROVIDE INFORMATION.