Permit: T06CM04858
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 03/05/2008 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) PROVIDE LETTER OF TORQUE FOR SWITCH GEAR 2) RECEIVED LETTER FROM ENGINEER FOR SERVICE CONDUCTOR SIZE |
|