Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM04846
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) REMOVE THE WHITE WIRES FROM CONDENSOR DISCONNECTS REPLACE WITH A BLACK WIRE 2) EXTEND WATER HEATER VENT MIN. 2' ABOVE WALL ON ROOF 3) VENT ON CONDENSATE MUST BE DOWNSTREAM OF THE TRAP 4) PROVIDE MIN. 1" CLEARANCE TO COMBUSTIBLES AROUND ENTIRE WATER HEATER VENT THRU ROOF |
|
09/20/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* |