Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH LOW VOLTAGE WIRING 2. HAVE OVERFILLED J-BOXES - 314.16 3. SUPPORT WIRES SECURED @ BOTH ENDS -- 300.11 4. MC SECURED WITHIN 12" OF TERMINATIONS -- 330.30 5. FINISH ALL WIRING ABOVE CEILING & WALK IN, PULL PROPER COLORS TO RTU -- 200.6 6. SERVICE BOND NEUTRAL TO DISCONNECT #4 FOR METER BASE BOND -- 250.66, 250.24 |