Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04846
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* INSTALL ALL J-BOXES (COVERS) TODAY BEFORE YOU LEAVE |
|
08/29/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio PREVIOUS CORRECTIONS NOT COMPLETED NEED TO PAY REINSPECTION FEE ALL J-BOXES TO BE OPEN NEXT INSPECTION & ELECTRICIAN ON SITE |
|
08/28/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LOW VOLTAGE WIRING NOT COMPLETE 2. HAVE OVERFILLED J-BOXES 3. HAVE LOOSE GROUND SCREWS IN J-BOXES 4. HAVE MISSING K.O IN J-BOX 5. STRAP EMT WITHIN 36" OF ENCLOSURES 6. TIGHTEN FITTINGS SET SCREWS 7. SEAL UNUSED RACEWAYS 8. STRAP FLEX FOR WALK IN CONDENSORS 9. GROUND ALL J-BOXES 10. SUPPORT WIRES TO BE SECURED @ BOTH ENDS 11. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH -- NEC 250.119 |
|
08/23/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |