Permit: T06CM04846

Parcel: 10511040D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM04846

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
INSTALL ALL J-BOXES (COVERS) TODAY BEFORE YOU LEAVE
08/29/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
PREVIOUS CORRECTIONS NOT COMPLETED
NEED TO PAY REINSPECTION FEE
ALL J-BOXES TO BE OPEN NEXT INSPECTION & ELECTRICIAN
ON SITE
08/28/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LOW VOLTAGE WIRING NOT COMPLETE
2. HAVE OVERFILLED J-BOXES
3. HAVE LOOSE GROUND SCREWS IN J-BOXES
4. HAVE MISSING K.O IN J-BOX
5. STRAP EMT WITHIN 36" OF ENCLOSURES
6. TIGHTEN FITTINGS SET SCREWS
7. SEAL UNUSED RACEWAYS
8. STRAP FLEX FOR WALK IN CONDENSORS
9. GROUND ALL J-BOXES
10. SUPPORT WIRES TO BE SECURED @ BOTH ENDS
11. EQUIPMENT GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH -- NEC 250.119
08/23/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*