Permit: T06CM04842

Parcel: 125011930

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/26/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
APPROVED PER APPEAL
02/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :$
PROVIDE APPROVED WAIVER OR MAKE CORRECTIONS
02/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROVIDE PROPER BONDING FOR CKT'S OVER 250V -
NEC 250.97 -- CHECK FOR RACEWAYS ON ALL ALTERED EQUIPMENT TO INSURE FAULT PATH IS RELIABLE.
2. IDENTIFY ALL EQUIPMENT PER PLAN
3. STILL DO NOT HAVE PROPER WORKING CLEARANCES FOR EQUIPMENT -- NEC 110.26
01/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. LABEL DISCONNECTS & EQUIPMENTS
2. MAINTAIN WORKING CLEARANCES 110.26
3. TIGHTEN LOOSE FITTINGS.
4. BOND ENCLOSURES
5. BOND BUSHINGS NEEDED AT CONCENTRICS 250.97
6. ELECTRICAL WORK NOT REFLECTED AS PER PLANS.
01/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE THE ELECTRICIAN ON SITE TO OPEN EQUIPMENT,
PROVIDE ACCESS ETC.

ALL EQUIPMENT TO BE IDENTIFIED, HAVE PLANS FOR INSPECTION.