Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM04838
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CLOSED FLANGES OK ROOF DRAIN MATERIAL ABS IN RETURN AIR/ P READ AUTHORIZATION TO WRAP PIPE OK |
|
07/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE LISTING FOR OFFSET CLOSET FLANGE TO BE USED AS A 3" AND A 4" FLANGE |
|
07/05/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SCREW FLANGES TO THE FLOOR AS REQUIRED 2. ALL OPEN PIPING TO REMAIN CAPPED |
|
07/03/2007 | PLUMBING - INTERMEDIATE | Cancelled | ||
05/15/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WEST OF TOILET ROOM #126 N/H MAY NOT BE SUPPORTED BY THE FITTING NEED TO SEE CLOSET FLANGES |
|
04/30/2007 | PLUMBING - INTERMEDIATE | Partial Approval | OK TO COVER EAST OF TOILET ROOM #126 | |
04/27/2007 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - AP canceled | |
04/13/2007 | PLUMBING - INTERMEDIATE | Partial Approval | PRE-SLAB PLUMBING OK AFTER HRS. $108.00 FEE PAID CHECK #35397 CAYLOR CONST. |
|
04/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | 1) OK TO COVER ALL AREAS ON THE SECOND FLOOR | |
04/06/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO POUR EAST HALF |
|
04/04/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ALL PIPING IS TO BE SUPPORTED AT EACH FLOOR HORIZONTAL PIPING OVERHEAD REQUIRES HANGER |
|
04/02/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPORT VERTICAL PIPE TEST OK 3/4" TO DISHWASHER OK |
|
03/28/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSPECTED PER UNAPPROVED PLAN REVISION UPSTAIRS TOILET RM, OK. INSULATE HW AND CW PER SPEC BOOK AT DISHWASHER 3/4" SPECIFIED FOR HW AT REAR SINK OFFSET VENT, OR INSTALL CASTIRON IN RETURN AIR PLENUM. PVC PIPING ALLOWED IN CONCEALED WALLS ONLY SEE SPEC 5.2.4 BUILDING HAS A RETURN AIR PLENUM |