Permit: T06CM04838

Parcel: 10821018X


Addresses:

4291 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM04838

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/04/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CORRECTIONS IN PROGRESS
08/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CT CONTROL UNIT TO HAVE SUPPLY CONDUCTORS IN RACEWAY
2. INSTALL ALL ENCLOSURE COVERS
3. GROUND ALL CONTROL UNIT ENCLOSURES
4. INSTALL PROTECTIVE BUSHINGS FOR #4A LARGER CONDUCTOR
5. PLAN REVISIONS TO BE APPROVED THROUGH PLAN REVIEW

FIELD EVALUATION LETTER FOR MRI RECEIVED TODAY
X-RAY ROOM IN PROGRESS MRI ROOM STILL TO BE INSPECTED
PREVIOUS CORRECTIONS IN PROGRESS.
08/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AT EXTERIOR GRADE LEVEL CHILLERS
a. PROTECT EMT
b. NEED SERVICE RECEPT.
2. NEED EMERGENCY LIGHT @ STAIR BOTTOM, E-LIGHT IN PET SCAN NOT WORKING, 2ND LEVEL E-LIGHTS NOT WORKING

NOTE: CT FIELD EVALUATION RECEIVED TODAY, LETTER FROM ENGINEER TO BE SEALED ANY ALTERATIONS TO APPROVED PLANS TO BE REVISED.
08/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION CALL IN FOR 8/17/07

1. STRUCTURE NOT TO BE OCCUPIED BEFORE APPROVAL
2. DOORS TO REMAIN UNLOCKED FOR INSPECTION
3. X-RAY ROOM NOT COMPLETE
08/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR SECOND LEVEL
1. HALL LIGHTING NOT PER PLAN
2. LIGHT NOT WORKING NEXT TO BREAK ROOM
3. WHAT IS COUNTER SWITCH FOR?
4. PACS ROOM AC OVERFUSED, RECEPTACLES MISSING COVERS, LIGHT NOT WORKING
08/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY - ROOFTOPS

INSPECTION FOR WEST ROOF
1. SECURE UNITS TO ROOF - NEC 110.13
2. STRAP FLEX WITHIN 12" OF TERMINATIONS
3. IDENTIFY DISCONNECTS, INSTALL PROPER SIZE FUSES/BREAKER
4. RE-ROUTE FLEX IN FRONT OF DISCONNECT - NEC 110.26

INSPECTION FOR CENTER ROOF
1. IDENTIFY AC 1 & AC 2