Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM04838
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/04/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS IN PROGRESS |
|
08/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CT CONTROL UNIT TO HAVE SUPPLY CONDUCTORS IN RACEWAY 2. INSTALL ALL ENCLOSURE COVERS 3. GROUND ALL CONTROL UNIT ENCLOSURES 4. INSTALL PROTECTIVE BUSHINGS FOR #4A LARGER CONDUCTOR 5. PLAN REVISIONS TO BE APPROVED THROUGH PLAN REVIEW FIELD EVALUATION LETTER FOR MRI RECEIVED TODAY X-RAY ROOM IN PROGRESS MRI ROOM STILL TO BE INSPECTED PREVIOUS CORRECTIONS IN PROGRESS. |
|
08/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AT EXTERIOR GRADE LEVEL CHILLERS a. PROTECT EMT b. NEED SERVICE RECEPT. 2. NEED EMERGENCY LIGHT @ STAIR BOTTOM, E-LIGHT IN PET SCAN NOT WORKING, 2ND LEVEL E-LIGHTS NOT WORKING NOTE: CT FIELD EVALUATION RECEIVED TODAY, LETTER FROM ENGINEER TO BE SEALED ANY ALTERATIONS TO APPROVED PLANS TO BE REVISED. |
|
08/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION CALL IN FOR 8/17/07 1. STRUCTURE NOT TO BE OCCUPIED BEFORE APPROVAL 2. DOORS TO REMAIN UNLOCKED FOR INSPECTION 3. X-RAY ROOM NOT COMPLETE |
|
08/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SECOND LEVEL 1. HALL LIGHTING NOT PER PLAN 2. LIGHT NOT WORKING NEXT TO BREAK ROOM 3. WHAT IS COUNTER SWITCH FOR? 4. PACS ROOM AC OVERFUSED, RECEPTACLES MISSING COVERS, LIGHT NOT WORKING |
|
08/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY - ROOFTOPS INSPECTION FOR WEST ROOF 1. SECURE UNITS TO ROOF - NEC 110.13 2. STRAP FLEX WITHIN 12" OF TERMINATIONS 3. IDENTIFY DISCONNECTS, INSTALL PROPER SIZE FUSES/BREAKER 4. RE-ROUTE FLEX IN FRONT OF DISCONNECT - NEC 110.26 INSPECTION FOR CENTER ROOF 1. IDENTIFY AC 1 & AC 2 |