Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04838
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/06/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/09/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* REVISE PLANS TO SHOW ACTUAL SCOPE OF ELECTRICAL WORK |
|
07/31/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE AREAS EXCEPT AS NOTED 1. CORDS NOT ALLOWED ABOVE CEILING - 400.7 & 8 2. VDV CABELING WHEN SUPPORTED BY WIRES TO BE AS PER 300.11 3. SECURE FIXTURES TO GRID 410.16 - MANUFACTURES CLIPS TO BE EFFECTIVE 4. BOX OVERFILL IN CANS |
|
07/24/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK AREA & CEILING TILES EXCEPT X-RAY PAINT FIRE ALARM ENCLOSURES REMOVE TEMP WIRING |
|
07/19/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK 2ND LEVEL SUSPENDED CEILING TILE INSTALLATION |
|
07/17/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS DO NOT CALL BEFORE COMPLETE OK A FEE MAY BE CHARGED |
|
07/05/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK FLOOR RACEWAYS CT ROOM -- 2 3/4 & 1 - 3" PER PHONE CONVERSATION |
|
07/03/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* OK WALL COVER EXTERIOR ROOM #101 SOUTH WALL MRI ROOM NOT COMPLETE DO NOT INSTALL ANY TILES IN CEILINGS BEFORE APPROVAL |