Permit: T06CM04838

Parcel: 10821018X


Addresses:

4291 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04838

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/06/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
07/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CT ROOM WALLS
07/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE CHILLER FOR MAGNET ONLY
*NOTE: ELECTRICAL FOREMAN TO CHECK S.C RATINGS FOR EQUIPMENT START AT SERVICE & WORK THROUGH
06/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PERFORMANCE TEST (LETTER RECEIVED TODAY)
2. OK BOND (MAIN) JUMPER SERVICE
3. OK FIRE SPRINKLER BOND
4. FINISH CHILLER WIRING & CALL FOR INSPECTION BEFORE YOU ENERGIZE.
06/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED A PASSING PERFORMANCE TEST REPORT NEC 230.95 C
2) TAP HOLE FOR MAIN BONDING JUMPER
3) BOND SPRINKLER PIPE
4) I WILL APPROVE TEP. DO NOT ENERGIZE THE SERVICE OR ANY EQUIPMENT BEFORE APPROVAL. KEEP LOCKED OFF. TEMP SERVICE LATERAL TO BE REMOVED AT SAME TIME
06/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO INSPECTION AT THIS TIME
1. FINISH SERVICE WIRING/BONDING
2. FINISH GROUNDING ELECTRODE SYSTEM
3. NEED TO HAVE SERVICE PERFORMANCE TESTED
4. PROVIDE TORQUE LETTER

DO NOT CALL BEFORE COMPLETE
06/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK RECEPTION AREA HALF WALL (NORTH MOST)
06/06/2007 ELECTRIC - INTERMEDIATE Partial Approval
06/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SOFFIT LIGHTING IN WAITING & RECEPTION AREAS
05/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER AREA "A"
EXCEPT MRI WALL
05/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER AREA "A" -- MAIN LEVEL, WEST OF ENTRY DOORS TO LINE 2-4
05/16/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
AREAS WEST OF ENTRY DOORS HAVE NOT BEEN APPROVED TO INSULATE OR DRYWALL AND MUST BE OPEN FOR INSPECTION
1 SIDE DRYWALL OK
05/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER PART "B" -- EAST OF ENTRY DOORS, MAIN LEVEL
ALSO, J-BOXES FOR EXTERIOR LIGHTING WILL BE BROUGHT OUT OF WALLS BEFORE COVER.
05/07/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK ONE SIDE DRYWALL PART B AREA
1. NEED NAIL PLATES WHERE AC CABLE LESS THAN 1 1/4" FROM STUD FACE.
2. GROUND BOXES
3. SECURE AC WITHIN 12" OF TERMINATIONS
4. BRING BOXES FLUSH TO WALLS
5. USE 277V COLORS FOR LIGHTING CKTS
6. FIRE ALARM BOXES TO BE RED
7. CHECK #151 WIRING @ PULL ALARM?
8. TIGHTEN LOCK NUTS & FITTINGS (OVER 250V RACEWAYS)
05/01/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
THE SHELL PERMIT FOR THIS STRUCTURE HAS NOT BEEN CALLED IN. IT MUST BE CALLED IN AND FINALED BEFORE FURTHER ELECTRICAL COVER WILL BE APPROVED. PLANS FOR SHELL TO BE ON SITE FOR THAT INSPECTION.
04/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SECOND LEVEL WALL COVER