Permit: T06CM04838

Parcel: 10821018X


Addresses:

4291 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM04838

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
09/06/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
06/18/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
06/06/2007 ELECTRIC - UNDERGROUND Partial Approval AT SERVICE
1. UNDERGROUND AT PAD FOR SERVICE ENT SECTION
2. (3) 4" PVC'S TO TEP TRANS, (3) 4" 90 DEG. STEEL EL'S AT SECONDARY INTO BUILDING, ALSO 1 1/4" PVC SERVICE.
3. X-RAY ROOM UNDERGROUND AND INTERMEDIATE SEE SHEET E3.1B NOTE ONE - REFER TO VENDOR DRAWINGS FOR CONDUITS REQUIRED. OK PER UMC IMAGING LAYOUT FOR X-RAY ROOM
OK TO COVER J-BOX, (6) 2 1/2" PVC CONDUITS, 1 1/4" PVC CONDUIT, (2) 2" PVC CONDUITS, ALSO OUTLETS & TELEDATA IN CONTROL ROOM OK
03/29/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UNDER SLAB COVER
*NOTE: PROVIDE CLARIFICATION ON GROUNDING ELECTRODE DETAIL AND HOW EXISTING HOUSE PANEL WILL BE RE-FED.
03/27/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
WORK IN PROGRESS
NOTE: DO NOT CALL FOR INSPECTION BEFORE WORK IS COMPLETE OR A REINSPECTION FEE MAY BE CHARGED.
03/26/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 3-4" PVC FOR "MOP" FEEDERS
2) NOTE: PATIENT CARE AREAS TO BE PER 517.13