Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM04837
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/08/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT VDV CABELING AS PER 725.3 & 6, 800.3 & 6, 300.11 2) SUPPORT M/C CABLE 12" + 300.11 3) OK TO TILE EXCEPT AS NOTED |
|
11/07/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUPPORT MC WITHIN 12" AT TERMINATION AND AT 6' INTERVALS PER CODE. LENGHTS 6' OR LESS FOR LIGHT FIXTURE EXTENT. |