Permit: T06CM04837

Parcel: 11011368C

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM04837

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
11/15/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CALLED CONTRACTOR, LET HIM KNOW PM INSPECT MAY NOT BE POSSIBLE DUE TO INSPECTOR OFF
11/15/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/06/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK STUD FRAME WALLS EXCEPT BATHROOMS.
11/02/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROTECT M/C CABLE AND FLEX CONDUIT AT STUDS
2) SUPPORT M/C CABLE 12" FROM BOXES
3) PLEASE OPEN PLYWOOD WALLS TO INSPECT ELECTRIC
4) GROUND METAL BOXES
5) NOTE: MAINTAIN WORKING CLEARANCES AT PANELS
6) PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE