Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM04837
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/15/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CALLED CONTRACTOR, LET HIM KNOW PM INSPECT MAY NOT BE POSSIBLE DUE TO INSPECTOR OFF |
|
11/15/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/06/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK STUD FRAME WALLS EXCEPT BATHROOMS. |
|
11/02/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) PROTECT M/C CABLE AND FLEX CONDUIT AT STUDS 2) SUPPORT M/C CABLE 12" FROM BOXES 3) PLEASE OPEN PLYWOOD WALLS TO INSPECT ELECTRIC 4) GROUND METAL BOXES 5) NOTE: MAINTAIN WORKING CLEARANCES AT PANELS 6) PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE |